bionlongisland.blogg.se

Firelite voice evac
Firelite voice evac









  1. #Firelite voice evac generator
  2. #Firelite voice evac full

Integral piezo provides local audible indication for troubles.Independent Form-C trouble relay allows FACP to monitor voice system while in active (alarm) state.

#Firelite voice evac generator

  • Integral diagnostic LEDs include: Power, System Trouble, Microphone Trouble, Message Generator Trouble, Tone Generator Trouble, Amplifier Fault, and others.
  • Zone 1 switch-programmable for All-Call operation.
  • Dual-optically-isolated, trigger input circuits are independently field-programmable for activation by polarity reversal (host FACP NAC) or dry-contact closure.
  • Speaker zone control via CMD inputs or keypad.
  • Alert tone selection may be field-programmed to conform with ANSI S3.41 Audible Emergency Evacuation Signal (Temporal Pattern), per NFPA.
  • Field-selectable lead-in/trailing tone selection.
  • Built-in alert tone generators with steady, slow whoop, high/ low, or chime tone capability.
  • Digital message may be field-selected for 3, 4, 6, 8, or infinite repeat.
  • Custom messages are field recordable, using the integral microphone or the audio input jack.
  • Integral digital message generator with standard, factory prerecorded emergency evacuation message.
  • Optional equipment: second amplifier local playback speaker and remote microphone.
  • Two Form-C trouble relays (System & AC Power Loss).
  • Nineteen different system and diagnostic LEDs.
  • Command inputs allow: – One 60-second message.
  • Three command input circuits activate on contact closure.
  • Two command input circuits can be independently field-programmed for activation by a Notification Appliance Circuit (NAC) or contact closure.
  • Five Command Input Circuits (CMD) are available for activation by an FACP.
  • Modular design for maximum system flexibility and ease of service.
  • Integral 25 watt, 25 VRMS audio amplifier with single Style Z (Class A) or Style Y (Class B) speaker circuit (expandable to 50 watts using the ACC-AAM25).
  • Listed to UL Standard 864, 9th edition.
  • Suitable Applications include schools, auditoriums, dormitories, theatres, restaurants, places of worship, lodging, office buildings, and factories. A host of field-programming options, including the capability of five custom messages (fire, tornado, evacuation, hazmat, nonfire, multi-language, etc.) make the ACC-25/50 the most versatile voice evacuation system available. A 70.7 VRMS converter is also available for independently converting amplifiers to meet retrofit needs. An optional 25 watt, 25 VRMS audio amplifier is available for system expansion to 50 watts (providing dual 25watt speaker circuits) or as a secondary amplifier in jurisdictions requiring backup. The ACC-25/50 is suitable for use as an adjunct (slave or stand-alone) to most UL-Listed Fire Alarm Control Panels (FACPs). The integral power supply charges up to 18 AH batteries, which can be housed in the ACC-25/50 cabinet.

    #Firelite voice evac full

    Significant technological enhancements set the ACC-25/50 apart from other EVAC panels - these include full supervision in both active (alarm or music) and standby conditions, supervision of amplifier outputs, field wiring, message generator, all tone generators, and the microphone. The ACC-25/50 records five field-programmable messages (up to 60 seconds total message duration) with an integral commercial-grade emergency communications microphone or from an external audio source. UPC: 783008112110 For more information about the Fire-Lite ECC-50/100, please contact us.ACC-25/50 Audio Command Center-25/50 VoiceEvacuation Control Panel General The ACC-25/50 (ACC-25/50) is a state-of-the-art, single- or dual-circuit (25 watts each) Emergency Voice Evacuation Control Panel (EVAC). Maximum Charger Capacity: 26 Amp Hour battery.Maximum Charging Circuit: Normal Flat Charge - 27.3V 2.8 amps.Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation.Eight Command Input Circuits to activate messages 1 to 8.Optional 70.7 VRMS conversion transformer available for the primary amplifier.

    firelite voice evac

  • 2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols.
  • 50 watts of 25 VRMS audio power (expandable to 100 watts).
  • firelite voice evac firelite voice evac

    Removable terminal blocks for ease of servicing and module replacement.Modular design for maximum system flexibility and easy expansion.

    firelite voice evac

    The power supply is built in and includes switch mode technology that delivers power to the panel and attached battery charger. The panel operates at 120VAC.Ĭapable of distributing up to 8 speaker circuits, all circuits can be wired in either Class B or Class A configuration. The Fire-Lite ECC-50/100 is an emergency voice evacuation panel for fire applications that can store a maximum of fourteen programmable messages up to 60 seconds each. Fire-Lite ECC-50/100 Single Speaker Emergency Voice Evacuation System, Integral Microphone, Tone Generator, 14 Recordable Messages, 120V